• Digital Fault Recorder-AMT-7000 image01
  • Digital Fault Recorder-AMT-7000 image02

AMT-7000 Digital Fault Recorder

AMT-7000 is a highly accurate multipurpose power system recorder equipped with various functions to monitor and record electric power system such as DFR,SER, PMU and DDR.

AMT-7000 is a highly accurate multipurpose power system recorder equipped with various functions to monitor and record electric power system such as DFR,SER, PMU and DDR.

FEATURES

Multiple functions

・Digital Fault Recording (DFR)
・Dynamic Disturbance Recording (DDR)
・Phasor Measurement Unit (PMU)
・Sequence of Event Recording (SER)

256spc sampling

・Sampling by 256 spc highly accurate measurement and recording.

Multiple input elements

・Up to 64 analog inputs and 128 digital inputs.

IEC61850 Compliant

・Complies with IEC61850 and can subscribe GOOSE message from station bus, trigger DFR and record to DFR and SER.

COMTRADE Format

The data format is in accordance with IEEE Std C37.111-2013 (COMTRADE).

Human machine interfaces

・5.7 inch color LCD with touch panel is equipped.
・Build-in web server provides browser based HMI.

Various time correction method

・GPS, IRIG-B, NTP

PC software

・Data manager automatically receives data from the AMT-7000 and manages it.
・Waveform analysis software supports various analysis such as detailed waveform display, waveform composition.

Catalog / Documents

CATALOG Product catalog(2.29MB)

Inquiry

Please feel free to contact us for quotations and consultations.